Electrical installation

Wiring of the control connections
Device variant with "Safe torque off" function

5

l

196

EDKVS9332X DE/EN/FR 6.1

Supply via internal voltage source

ƒ

If a freely assignable digital output (e.g. X5/A1) is set to HIGH level, it serves as an
internal voltage source. An output can be loaded with a maximum of 50 mA.
– You can supply a voltage to the relay K

SR

and two digital inputs (X5/28 and e.g.

X5/E1) via a digital output.

– You must connect two digital outputs in parallel and set them to HIGH level for

the maximum wiring (relay K

SR

and X5/E1 ... X5/E5).

ƒ

For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
freely assignable analog output (e. g. X6/63) permanently to HIGH level.

GND2

+24V

+5 V

E5

A2 A3 A4 ST1ST2 59

39

3k

47k

50mA

50mA

50mA

50mA

X5

28 E1 E2 E3 E4

3k

3k

3k

3k

3k

X11 K31 K32 33 34

S1

S2

IN1 IN2 IN3 IN4

+

K

SR

A1

Z1

X3

GND1

GND1

X6

1

AIN1

AIN2

AOUTx

AOUT2

AOUT1

2

3

4

1

3

2

4

7

10k

10k

7

7

62 63

242R

1
2
3
4
5
6

100k

100k

100k

100k

3.3nF

Z

Z

9300std074

Fig. 5−28

Wiring of digital and analog inputs/outputs with active "Safe torque off" function and internal
voltage source

S1

Deactivate pulse inhibit (1st disconnecting path)

S2

Enable controller (2nd disconnecting path)

Z1

Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function

X5/A4 Feedback via a digital output (e. g. DIGOUT4)

NO contact or NC contact

Z

Load
Minimum wiring required for operation

Terminal assignment in the Lenze setting: