Electrical installation, Supply via internal voltage source, And x5/e1 ... x5/e5) – Lenze 9300 0.37kW-75kW User Manual
Page 196
![background image](/manuals/566007/196/background.png)
Electrical installation
Wiring of the control connections
Device variant with "Safe torque off" function
l
196
EDKVS9332X DE/EN/FR 6.1
Supply via internal voltage source
ƒ
If a freely assignable digital output (e.g. X5/A1) is set to HIGH level, it serves as an
internal voltage source. An output can be loaded with a maximum of 50 mA.
– You can supply a voltage to the relay K
SR
and two digital inputs (X5/28 and e.g.
X5/E1) via a digital output.
– You must connect two digital outputs in parallel and set them to HIGH level for
the maximum wiring (relay K
SR
and X5/E1 ... X5/E5).
ƒ
For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
freely assignable analog output (e. g. X6/63) permanently to HIGH level.
GND2
+24V
+5 V
E5
A2 A3 A4 ST1ST2 59
39
3k
47k
50mA
50mA
50mA
50mA
X5
28 E1 E2 E3 E4
3k
3k
3k
3k
3k
X11 K31 K32 33 34
S1
S2
IN1 IN2 IN3 IN4
+
K
SR
A1
Z1
X3
GND1
GND1
X6
1
AIN1
AIN2
AOUTx
AOUT2
AOUT1
2
3
4
1
3
2
4
7
10k
10k
7
7
62 63
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
Z
Z
9300std074
Fig. 5−28
Wiring of digital and analog inputs/outputs with active "Safe torque off" function and internal
voltage source
S1
Deactivate pulse inhibit (1st disconnecting path)
S2
Enable controller (2nd disconnecting path)
Z1
Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function
X5/A4 Feedback via a digital output (e. g. DIGOUT4)
NO contact or NC contact
Z
Load
Minimum wiring required for operation
Terminal assignment in the Lenze setting:
^ 199