Electrical installation – Lenze 9300 0.37kW-75kW User Manual

Page 181

Advertising
background image

Electrical installation

Standard devices with a power of 45 kW

Motor connection

5

l

181

EDKVS9332X DE/EN/FR 6.1

Characteristics of the connection for motor temperature monitoring:

Terminals T1, T2

Connection

l

PTC thermistor
– PTC thermistor with defined tripping temperature (acc. to DIN 44081 and

DIN 44082)

l

Thermal contact (NC contact)
– Thermostat as NC contact

Tripping point

l

Fixed (depending on the PTC/thermal contact)

l

PTC: R

J

>

1600

W

l

Configurable as warning or error (TRIP)

Notes

l

Monitoring is not active in the Lenze setting.

l

If you do not use a Lenze motor, we recommend the use of a PTC thermistor up
to 150°C.

T1

T2

PE

U

V

W

2
3

0
4

T1
T2

2.5 Nm
22.1 lb-in

U, V, W,
PE

M8
15 Nm
132 lb-in

1

M5 x 12
3 Nm (26.5 lb-in)

}

+

PE

9300std031

Fig. 5−17

Motor connection with PTC thermistor or thermal contact (NC contact)

0 PE stud

PE cable connection with ring cable lug

1 U, V, W

Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 120 mm

2

with ring cable lug

2 Shield clamps

Place shields of motor cable with large surface on the shield sheet and fasten with shield
clamps and M5 × 12 mm screws

3 Cable ties

Strain relief of motor cable

4 T1, T2 for motor temperature monitoring

Cable connection for PTC thermistors or thermal contacts (NC contacts)
Place shield with large surface on PE stud

Motor with KTY thermal sensor

)

Note!

ƒ

We recommend to use Lenze system cables for wiring.

ƒ

For self−made cables only use cables with shielded cores twisted in pairs.

Advertising