Mains choke/mains filter assignment, Electrical installation, Installation to ul – Lenze 9300 0.37kW-75kW User Manual
Page 170: 4 mains choke/mains filter assignment
![background image](/manuals/566007/170/background.png)
Electrical installation
Standard devices in the power range 15 ... 30 kW
Mains choke/mains filter assignment
l
170
EDKVS9332X DE/EN/FR 6.1
Installation to UL
Supply conditions
Range
Description
Fuses
l
Only according to UL 248
l
Mains short−circuit current up to 5000 A
rms
: All classes permissible
l
Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R" permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation with mains choke/mains filter
EVS9327−xx
35
8
EVS9328−xx
60
4
EVS9329−xx
80
4
5.5.4
Mains choke/mains filter assignment
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVS9327−xx
ELN3−0088H035−001
EZN3A0110H030
25
E82ZN22334B230
10
E82ZZ15334B230
1)
10
E82ZN22334B230
50
EZN3B0110H030U
2)
50
E82ZZ15334B230
1)
50
EVS9328−xx
ELN3−0075H045
EZN3A0080H042
25
E82ZN22334B230
10
E82ZN22334B230
50
EZN3B0080H042
50
EVS9329−xx
ELN3−0055H055
EZN3A0055H060
25
E82ZN30334B230
10
E82ZN30334B230
50
EZN3B0055H060
50
1)
RFI filter
2)
Footprint filter