Mechanical installation
Standard devices in the power range 0.37 ... 11 kW
Mounting in "cold plate" technique
l
138
EDKVS9332X DE/EN/FR 6.1
4.1.4
Mounting in "cold plate" technique
The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on collective coolers.
For this purpose, the drive controllers of type EVS93xx−Cxx must be used.
Mounting material required from the scope of supply:
Description
Use
Quantity
EVS9321−Cx
EVS9322−Cx
EVS9323−Cx
EVS9324−Cx
EVS9325−Cx
EVS9326−Cx
Fixing bracket
Controller fixing
2
2
2
Sheet metal screw
3.5 × 13 mm (DIN 7981)
Mounting the fixing bracket
to the controller
6
6
6
Requirements for collective coolers
The following points are important for safe and reliable operation of the controller:
ƒ
Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at
least as large as the cooling plate of the controller.
– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all
specified screw connections.
ƒ
Observe the thermal resistance R
th
given in the table. The values are valid for
controller operation under rated conditions.
9300
Cooling path
Power to be dissipated
Heatsink − environment
Type
P
v
[W]
R
th
[K/W]
EVS9321−Cx
24
1.45
EVS9322−Cx
42
0.85
EVS9323−Cx
61
0.57
EVS9324−Cx
105
0.33
EVS9325−Cx
180
0.19
EVS9326−Cx
360
0.10
Ambient conditions
ƒ
The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.
ƒ
Temperature at the cooling plate of the drive controller: max. 75 °C.