Mechanical installation

Standard devices in the power range 0.37 ... 11 kW
Mounting in "cold plate" technique

4

l

138

EDKVS9332X DE/EN/FR 6.1

4.1.4

Mounting in "cold plate" technique

The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on collective coolers.
For this purpose, the drive controllers of type EVS93xx−Cxx must be used.

Mounting material required from the scope of supply:

Description

Use

Quantity

EVS9321−Cx
EVS9322−Cx

EVS9323−Cx
EVS9324−Cx

EVS9325−Cx
EVS9326−Cx

Fixing bracket

Controller fixing

2

2

2

Sheet metal screw
3.5 × 13 mm (DIN 7981)

Mounting the fixing bracket
to the controller

6

6

6

Requirements for collective coolers

The following points are important for safe and reliable operation of the controller:

ƒ

Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at

least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all

specified screw connections.

ƒ

Observe the thermal resistance R

th

given in the table. The values are valid for

controller operation under rated conditions.

9300

Cooling path

Power to be dissipated

Heatsink − environment

Type

P

v

[W]

R

th

[K/W]

EVS9321−Cx

24

1.45

EVS9322−Cx

42

0.85

EVS9323−Cx

61

0.57

EVS9324−Cx

105

0.33

EVS9325−Cx

180

0.19

EVS9326−Cx

360

0.10

Ambient conditions

ƒ

The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.

ƒ

Temperature at the cooling plate of the drive controller: max. 75 °C.