Electrical installation
Wiring of digital frequency input / digital frequency output
l
208
EDKVS9332X DE/EN/FR 6.1
5.11
Wiring of digital frequency input / digital frequency output
Installation material required from the scope of supply:
Description
Use
Quantity
Protective cover
Protection for unused Sub−D connections
4
Technical data
Field
Digital frequency output X10
Connection at drive controller
Connector: Socket, 9−pole, Sub−D
Pin assignment
Dependent on the selected basic configuration
Output frequency
0 ... 500 kHz
Signal
Two−track with inverse 5 V signals (RS422) and zero track
Load capacity
Max. 20 mA per channel
(up to 3 slave drives can be connected)
Special features
The "Enable" output signal at X10/8 switches to LOW if the drive
controller is not ready for operation (e.g. disconnected from mains). This
can trip SD3 monitoring on the slave drive.
Internal voltage source
(X10/4, X10/5)
DC 5 V / max. 50 mA
Total current at X9/4, X9/5 and X10/4, X10/5: max. 200 mA
Field
Digital frequency input X9
Connection at drive controller
Connector: Pin, 9−pole, Sub−D
Input frequency
0 ... 500 kHz (TTL level)
Signal
Two−track with inverse 5 V signals (RS422) and zero track
Signal evaluation
Via code C0427
Current consumption
Max. 5 mA
Special features
With activated SD3 monitoring, TRIP or warning is tripped if the "Lamp
Control" input signal at X9/8 switches to LOW.
Due to this the drive controller can respond if the master drive is not ready
for operation.
Wiring
)
Note!
ƒ
We recommend to use Lenze system cables for wiring.
ƒ
For self−made cables only use cables with shielded cores twisted in pairs.