With hand terminal

EDK71MMXXX−010 DE/EN/FR 5.0

L

102

The

user menu is set to all codes at the factory to allow for commissioning a standard application:

)

Note!

Settings for "Motor 2" are not relevant for the starttec "Motor starter
type 1"! (Corresponding information applies only to the starttec "Motor
starter type 2" for operation with 2 motors.)

Code

Designation

Lenze setting

C0054 Apparent motor current of

motor 1

Display only

C0055 Apparent motor current of

motor 2

Display only

C0006 Transfer HW/hand terminal

0

Setting the acceleration time (C0012) and starting voltage
(C0016) via potentiometer, setting the rated motor current
(C0120) via stepping switch

C0120 Rated current

Rated motor current for I

2

t monitoring

1 Motor 1

Accepts the value from the stepping switch:

l

If C0006 = 0, 2, 4, 6:
– Display only

l

If C0006 = 1, 3, 5, 7:
– Rated current can be set via C0120

2 Motor 2

C0410 Configuration of digital input

signals

1 Motor 1 start/stop

1

X3/E1

2 Motor 2 start/stop

2

X3/E2

3 Brake control

3

X3/E3

4 ... 24

255

Not assigned

C0415 Configuration of digital

output signals

1 X3/A1

3

Status of motor 1

2 X3/A2

4

Status of motor 2

3 X3/A3

5

Status of brake

4 X3/A4

25

TRIP error message

5 ... 6 AS−I output bit

255

Not assigned

C0012 Motor voltage acceleration

time

Time for voltage change U

0

... U

mains

1 Motor 1

Accepts the value from potentiometer "T"

l

If C0006 = 0, 1, 2, 3:
– Display only

l

If C0006 = 4, 5, 6, 7:
– Acceleration time can be set via C0012

2 Motor 2

C0423 Delay time of "Release

brake"

0.00 s

C0424 Delay time of "Apply brake"

0.00 s

C0002 Parameter set management

See code table