2 technical data, General data, Technical data – Lenze EDK71MMXXX−010 User Manual

Page 77

Advertising
background image

Technical data

General data

2

EDK71MMXXX−010 DE/EN/FR 5.0

77

L

Conformity

CE

Low−Voltage Directive (2006/95/EC)
EMC Directive (2004/108//EC)

Standards

DIN EN 60947−4−2

Semiconductor motor control devices and starters for AC
voltage

Vibration resistance

Accelerational stability up to 4 g (Germanischer Lloyd, general requirements)

Climatic conditions

Class 3K3 to EN 50178 (without moisture condensation, medium relative
humidity 85

%)

Degree of pollution

VDE 0110 Part 2, Degree of pollution 2

Permissible temperature
ranges

Transport

−25 °C ... +70 °C

Storage

−25 °C ... +60 °C

Operation

with motor mounting: −25 °C ... +60 °C
with wall mounting: −25 °C ... +40 °C

Permissible installation
height

0 ... 4000 m amsl
Above 1000 m amsl Reduce rated output current by 5 %/1000 m .

Mounting positions

Every mounting position and mounting direction is permissible.

Free space

Above

100 mm

Lateral

100 mm

EMC

−17−

Maintaining requirements to EN 61800−3/A11

Noise emission

Maintaining limit class B to EN 60947−4−2

Leakage current toward PE
(to EN 50178)

< 3.5 mA

Enclosure

−18−

(only with rubber cap on AIF
interface)

IP 65

NEMA 250 Type 4

Protective measures against

Motor overtemperature (input for PTC or thermal contact, I

2

t monitoring)

Protective insulation of
control circuits

Safe disconnection from mains:
Double/reinforced insulation to EN 50178

Insulation resistance

Overvoltage category III to VDE 0110

Advertising