Commissioning, Code table – Lenze EDK71MMXXX−010 User Manual

Page 124

Advertising
background image

7

Commissioning

Code table

EDK71MMXXX−010 DE/EN/FR 5.0

L

124

Code

IMPORTANT

Setting options

No.

Selection

Lenze

Designation

C0415

v

uSEr

Configuration of
digital output
signals

Output of internal digital signals to
terminals or AS interface

1 Digital output

X3/A1

3

Status of motor 1

Motor 1 is running

HIGH

Motor 1 is stopped LOW

2 Digital output

X3/A2

4

Status of motor 2 or direction of
rotation

Motor 2 is running
or CCW rotation

HIGH

Motor 2 stopped
or CW rotation

LOW

3 Digital output

X3/A3

5

Status of brake

Brake is released

HIGH

Brake is applied

LOW

4 Digital output

X3/A4

25

TRIP fault message

TRIP active

HIGH

No fault

LOW

5 AS−I status bit

D0

255

Not assigned

Only active for variant
E71MM402FxAxxx

6 AS−I status bit

D1

255

Not assigned

Internal digital signals

0

Not assigned

1

PAR−B0 active

2

starttec inhibited

3

Status of motor 1

4

Status of motor 2

5

Status of brake

6

Error in power section

7

fd = 0

8

starttec released/inhibited

9 ...
12

Reserved

13

Overtemperature" warning

14

Reserved

15

CCW rotation

16

Ready for operation

17

PAR−B1 active

18

Reserved

19

Motor overtemperature" warning

(PTC input)

Is generated only if
C0119 = 2