Electrical installation, Connection of bus function module – Lenze EDK71MMXXX−010 User Manual

Page 95

Advertising
background image

Electrical installation

Connection of bus function module

5

EDK71MMXXX−010 DE/EN/FR 5.0

95

L

Control of starttec with PROFIBUS−DP FIF module

The control of starttec via PROFIBUS−DP FIF module is possible via control word FIF−CTRL1 and status
word FIF−STAT1.

The following bit assignment applies:

Bit

Assignment of control word FIF−CTRL1

Assignment of status word FIF−STAT1

0

S1

Reserved

1

S2

Pulse inhibit (DCTRL1−IMP)
0 = power outputs released
1 = power outputs inhibited

2

Reserved

Reserved

3

Reserved

Reserved

4

Reserved

Reserved

5

Reserved

Reserved

6

Reserved

Fixed 1

7

Reserved

Controller inhibit (DCTRL1−CINH)
0 = controller released
1 = controller inhibited

8

Reserved

Device status (DCTRL1−STAT*1 ... DCTRL1−STAT*6)
0001 = switch−on inhibit
0011 = operation inhibited
0110 = operation released
1000 = fault active

9

Controller inhibit (FIF−CTRL1−CINH)
0 = controller released
1 = controller inhibited

10

External fault (FIF−CTRL1−TRIP−SET)

11

Reset fault (FIF−CTRL1−TRIP−RESET)
0 = a bit change causes TRIP reset

12

Reserved

Reserved

13

Reserved

Reserved

14

Reserved

Reserved

15

Reserved

Ready for operation (DCTRL1−RDY)
0 = not ready for operation (fault)
1 = ready for operation (no fault)