Commissioning

Code table

7

EDK71MMXXX−010 DE/EN/FR 5.0

113

L

Code

IMPORTANT

Setting options

No.

Selection

Lenze

Designation

C0054

uSEr

Apparent
current of
motor 1

0

{A}

50 Display only

C0055

uSEr

Apparent
current of
motor 2

0

{A}

50 Display only

C0061

Housing
temperature

0

{

°C}

255 Display only

l

If > +80 °C:

– starttec sets TRIP

OH

C0093

Device type

4020

Display only

C0094

Reserved

C0099

Software
version

x.y

Display only
x = main version, y = index

C0119

v

Configuration of
motor
temperature
monitoring (PTC
input)

1

0

PTC input inactive

Configure signal output in
C0415

1

PTC input active, TRIP occurs

2

PTC input active, warning occurs

C0120

uSEr

Rated motor
current

1.0

{0.1 A}

9.5 See nameplate of motor

1 Motor 1

а

а

Accepts the value from
the stepping switch

l

If C0006 = 0, 2, 4, 6:
– Display only

l

If C0006 = 1, 3, 5, 7:
– Rated motor current

adjustable via C0120

2 Motor 2

à

C0121

Tripping class

Tripping characteristic see
^ 79

1 Motor 1

2

Tripping class 10

2 Motor 2

2

Tripping class 10

0

I

2

t monitoring switched off

1

Tripping class 10A

2

Tripping class 10

3

Tripping class 20

4

Tripping class 30

C0122

Mains phase
failure message

0

0

TRIP

1

Warning

C0123

Message I

2

t

overload

0

0

TRIP

Change becomes effective
only after next release of
starttec

1

Warning