Electrical installation

Connection of spring−operated brake

EDK71MMXXX−010 DE/EN/FR 5.0

L

88

−22−

{

Danger!

All power connections (terminal strip X1) can carry dangerous electrical
voltages if the starttec is connected to the mains. For this reason,
de−energise the starttec before beginning to work on it or opening the
housing.

(

Stop!

If you use starttec to switch a spring−operated brake, the starttec type
E71MM402x4Axxx (brake voltage 180 VDC) must only be operated on mains
voltages

£ 400 V. Mains voltages > 400 V destroy the brake rectifier.

Note that the brake voltage at X1/B1, B2 is dependent upon the mains voltage:

starttec E71MM402x2Axxx

E71MM402x4Axxx

Mains voltage

Brake voltage at X1/B1, B2

U

B1B2

» 0.89 x U

L2BN

U

B1B2

» 0.45 x U

L1L2

3/PE AC 230 V

205 VDC

103 VDC

3(/N)/PE AC 400 V

205 VDC

180 VDC

3(/N)/PE AC 500 V

257 VDC

Operation not allowed