Technical data

Rated data

EDK71MMXXX−010 DE/EN/FR 5.0

L

78

Supply voltage

Voltage range

U

DC

+ 24 VDC (+18 VDC − 0 % ... +30 VDC + 0 %)

Current capacity at + 24 VDC

Min. 200 mA

Max. 1.5 A (digital inputs and outputs are completely
connected)

Motor switch

Mains voltage
(switched voltage)

U

N

3/PE AC 100 V − 0 % ... 550 V + 0 %;
45 Hz − 0 % ... 65 Hz + 0 %

Max. continuous output current

I

N

9.5 A (sum of output currents)

Cyclical switching

Max. 1 switching / s

Motor power (Lenze motors)

at 3/PE AC 230 V P

N

0.25 ... 2.2 kW

Max. 9.5 A

at 3(/N)/PE AC 400 V P

N

0.25 ... 4.0 kW

at 3(/N)/PE AC 500 V P

N

0.37 ... 5.5 kW

Brake switch

Output voltage

at 3/PE AC 230 V U

B

205 VDC

at 3(/N)/PE AC 400 V U

B

180 VDC, 205 VDC

at 3(/N)/PE AC 500 V U

B

257 VDC

Max. output current

I

B

0.4 A

Cyclical switching

Max. 3 switchings / s

Monitoring functions

Motor protection switch−function

I

2

t monitoring, adjustable tripping classes

(I

2

t tripping characteristic:

^ 79)

Class 10A

Max. I

r

= 9.5 A

Class 10

Max. I

r

= 9.0 A

Class 20

Max. I

r

= 8.0 A

Class 30

Max. I

r

= 7.0 A

Motor temperature

PTC thermistor (PTC) or thermal contact (NC contact)

Device protection

I

2

t monitoring (Class 10A) referenced to 9.5 A

Mains failure control

Yes

Load failure control

Yes, programmable switch−off limit