5

Electrical installation

Important notes

EDK71MMXXX−010 DE/EN/FR 5.0

L

84

{

Danger!

l

All power connections (terminal strip X1) can carry dangerous electrical
voltages if the starttec is connected to the mains. For this reason,
de−energise the starttec before beginning to work on it or opening the
housing.

−21−

l

All control terminals feature only basic insulation (single isolating
distance) after the connection of a PTC thermistor (PTC) or a thermal
switch (NC contact):

Protection against accidental contact with defective isolating distance
can only be ensured through external measures, e.g. double insulation.

)

Note!

Operation with motors < 250 W or with motor currents < 1 A in all
operating modes

The starttec is designed for motor powers of 250 W ... 4 kW or motor
currents of 1 A ... 9.5 A.

The following must be observed if you operate motors on the starttec with
powers < 250 W or rated currents < 1 A:

l

The internal I

2

xt monitoring cannot be used due to the low current:

Switch off the internal I

2

xt monitoring (C0121 = 0).

Monitor the motor temperature with a PTC or thermal contact (NC
contact)

In addition you can use suitable external motor protection switches.

l

During operation, the mains phase failure detection may respond
although no mains failure has occurred.

Adjust the mains phase failure detection to "warning" (C0122 = 1) so
that the drive does not switch off with an error message.