Commissioning

With hand terminal

7

EDK71MMXXX−010 DE/EN/FR 5.0

105

L

Switch−on sequence

Comment

9.

Set rated motor current in C0120/1

start017

00

01 20

001

1

c

d

j

g f k i h PS



w x

z
y

Rated motor current for I

2

t

monitoring
Accepts the value from the
stepping switch:

l

If C0006 = 0, 2, 4, 6:
– Display only

l

If C0006 = 1, 3, 5, 7:
– Rated current can be

set via C0120

10.

Configure digital input signals
Lenze setting:

l

C0410/1 = 1:
– X3/E1: motor 1 start/stop

l

C0410/2 = 2:
– Function is not active with

starttec type 1

l

C0410/3 = 3:
– X3/E3: brake control

start039

00

1

04 10

001

1

c

d

j

g f k i h PS



A

w x

z
y

Linking external signal
sources with internal digital
signals
For additional setting
options, see the code table
(

^ 107)

11.

Configure digital output signals
Lenze setting:

l

C0415/1 = 3:
– X3/A1: status of motor 1

l

C0415/2 = 4:
– Function is not active with

starttec type 1

l

C0415/3 = 5:
– X3/A3: brake status

l

C0415/4 = 25:
– X3/A4: Active error message

start040

00

3

04 15

001

1

c

d

j

g f k i h PS



A

w x

z
y

Output of status messages
to terminal or bus
For additional setting
options, see the code table
(

^ 107)

12.

Set acceleration time t

ir

in C0012/1

start038

00

0

00 12

001

1

c

d

j

g f k i h PS



A

w x

z
y

Time for voltage change
U

0

... U

mains

Accepts the value from
potentiometer "T"

l

If C0006 = 0, 1, 2, 3:
– Display only

l

If C0006 = 4, 5, 6, 7:
– Acceleration time can

be set via C0012