Setting of all important parameters

EDK71MMXXX−010 DE/EN/FR 5.0

L

96

Before commissioning, set important operating parameters with the potentiometers and the stepping
switch:

−24−

l

the rated motor current with the stepping switch

l

the acceleration time with potentiometer "T"

l

the starting voltage with potentiometer "U

0

"

Stepping switch [S]

Lenze motor power with mains voltage

Comment

Position

Rated current

3/PE 230 VA

C

3(/N)/PE 400

VAC

3(/N)/PE 500

VAC

0

No I

2

t monitoring

1

1.0 A

0.25 kW

0.37 kW

2

1.4 A

0.37 kW

0.55 kW

3

1.8 A

0.25 kW

0.55 kW

0.75 kW

4

2.4 A

0.37 kW

0.75 kW

1.1 kW

5

3.0 A

0.55 kW

1.1 kW

1.5 kW

6

4.0 A

0.75 kW

1.5 kW

2.2 kW

7

5.5 A

1.1 kW

2.2 kW

3.0 kW

8

7.0 A

1.5 kW

3.0 kW

4.0 kW

9

9.5 A

2.2 kW

4.0 kW

5.5 kW

Setting

Comment

1.

Set the rated motor current with the
stepping switch
Lenze setting: 1 = 1.0 A

start032

1.4 A

1.8 A

2.4

A

3.0 A

4.0

A

5.5 A

7.0 A

9.5

A

OFF

1.0

A

0 1 2

3

45

67

8

9

l

See also

^ 79

l

Use the hand terminal to
check or change the
setting in C0120

2.

Set the acceleration time t

ir

with

potentiometer T"
Lenze setting: approx. 1.5 s

start012

0

3.00 s

Use the hand terminal to
check or change the setting
in C0012

3.

Set the starting voltage U

0

with

potentiometer U

0"

Lenze setting: approx. 50 %

start008

0

100.0 %

l

With U

0

= 100 %, the

acceleration time t

ir

is

deactivated

l

Use the hand terminal to
check or change the
setting in C0016

start028

100%

0

0

t

Uout

Ustart