Commissioning, Code table – Lenze EDK71MMXXX−010 User Manual

Page 114

Advertising
background image

7

Commissioning

Code table

EDK71MMXXX−010 DE/EN/FR 5.0

L

114

Code

IMPORTANT

Setting options

No.

Selection

Lenze

Designation

C0126

s

Behaviour with
communication
error

10

Monitored communication channel

You activate a combination
of monitorings by entering
the sum of the selection
values

0

All monitorings deactivated

1

Process data channel of the AIF
interface

Communication abort with
active monitoring trips TRIP
CE0

2

Internal communication between
function module to FIF and drive
controller

Communication abort with
active monitoring trips TRIP
CE5

4

Communication (Bus OFF) in
operation with system bus (CAN)
function module to FIF

Communication abort with
active monitoring trips TRIP
CE6

8

Remote parameter setting via
C0370 in operation with system
bus (CAN) function module to FIF

Communication abort with
active monitoring trips TRIP
CE7

Advertising