Troubleshooting, Error messages – Lenze EDK71MMXXX−010 User Manual

Page 128

Advertising
background image

Troubleshooting

Error messages

?

EDK71MMXXX−010 DE/EN/FR 5.0

128

L

LEDs on starttec (operating status indicators)

−30−

LED

Operating status

green

red

on

off

starttec released

flashes

off

starttec inhibited

off

flashes in 1−second cycle

Fault active, control in C0161

Fault messages on the keypad or in the Global Drive Control parameter setting program

Display

Fault

Cause

Remedy

Keypad

PC

1)

noer

0

No fault

ccr

A

71

System fault

Strong interference injections on
control cables

Route control cable in shielded way

Ground or earth loop in the
wiring

ce1

A

62

Communication
error at CAN−IN1
with sync control

CAN−IN1 object receives faulty
data or communication is
interrupted

l

Check plug−in connection
of

ó

FIF bus module

l

Check transmitter

l

Increase monitoring time in
C0357/1, if necessary

ce2

A

63

Communication
error at CAN−IN2

CAN−IN2 object receives faulty
data or communication is
interrupted

l

Check plug−in connection
of

ó

FIF bus module

l

Check transmitter

l

Increase monitoring time in
C0357/2, if necessary

ce3

A

64

Communication
error at CAN−IN1
with event or time
control

CAN−IN1 object receives faulty
data or communication is
interrupted

l

Check plug−in connection
of

ó

FIF bus module

l

Check transmitter

l

Increase monitoring time in
C0357/3, if necessary

ce4

A

65

Bus Off
(many
communication
errors occurred)

Drive controller received too
many fault messages via system
bus and decoupled itself from
the bus

l

Check whether bus termination is
present

l

Check shield connection of cables

l

Check PE connection

l

Check bus load, reduce baud
rate, if necessary

ce5

A

66

CAN timeout

With remote parameter setting
via system bus (C0370):
Slave does not answer.
Communications monitoring
time is exceeded

l

Check wiring of system bus

l

Check system bus configuration

For operation with module on
FIF:
Internal error

Consultation with Lenze is required

EEr

A

91

External fault
(TRIP−SET)

A digital signal assigned with
the TRIP set function is activated

Check external encoder