Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual
Page 103
Advertising
Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
103
Using Explicit Messaging (Adapter mode only)
Chapter 6
ControlLogix Controller Example Ladder Logic Program to Write a
Single Parameter
A Set Attribute Single message is used to write to a single parameter. This write
message example writes a value to the 32-bit REAL (floating point) parameter
535 - [Accel Time 1] in a PowerFlex 750-Series drive.
Table 7 - Example Controller Tags to Write a Single Parameter
Figure 26 - Example Ladder Logic to Write a Single Parameter
Operand
Controller Tags for Single Write Message
Data Type
XIC
Execute_Single_Write_Message
BOOL
MSG
Single_Write_Message
MESSAGE