Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

37

Configuring the Option Module

Chapter 3

Setting the Subnet Mask

1.

Verify that

Device Parameter 05 - [Net Addr Sel] is set to “1”

(Parameters).

2.

Set the value of

Device Parameters 11 - [Subnet Cfg 1] through 14 -

[Subnet Cfg 4]

to the desired value for the subnet mask.

3.

Reset the option module; see

Resetting the Option Module on page 49

.

Setting the Gateway Address

1.

Verify that

Device Parameter 05 - [Net Addr Sel] is set to “1”

(Parameters).

2.

Set the value of

Device Parameters 15 - [Gateway Cfg 1] through 18 -

[Gateway Cfg 4]

to the IP address of the gateway device.

3.

Reset the option module; see

Resetting the Option Module on page 49

.

Default = 0.0.0.0 255 . 255 . 255 . 255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

Edit Subnet Cfg 1

0

0 << 255

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Default = 0.0.0.0

255 . 255 . 255 . 255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]

Edit Gateway Cfg 1

0

0 << 255

ESC

ENTER

Stopped

0.00 Hz

AUTO

F