Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

151

Option Module Parameters

Appendix B

11
12
13
14

[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Sets the subnet mask bytes for the option module’s network
address when Device Parameter 05 - [Net Addr Sel] is set to
“1” (Parameters) and the Node Address switches (

Figure 2 on

page 21

) are not being used (that is, switches set to any value

other than 001…254 or 888).

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required:

Yes

15
16
17
18

[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Sets the gateway address bytes for the option module’s network
address when Device Parameter 05 - [Net Addr Sel] is set to
“1” (Parameters) and the Node Address switches (

Figure 2 on

page 21

) are not being used (that is, switches set to any value

other than 001…254 or 888).

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required:

Yes

19

[Net Rate Cfg 1]
Sets the speed and duplex network data rate at which the option
module communicates on its ENET1 network port. (Updates
Device Parameter 20 - [Net Rate Act 1] after a reset.)

Default:

0 = Autodetect

Values:

0 = Autodetect
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
5 = Disabled

Type:

Read/Write

Reset Required:

Yes

20

[Net Rate Act 1]
Displays the actual speed and duplex network data rate for the
option module’s ENET1 network port.

Values:

0 = No Link
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
5 = Dup IP Addr

Type:

Read Only

21

[Net Rate Cfg 2]
Sets the speed and duplex network data rate at which the option
module communicates on its ENET2 network port. (Updates
Device Parameter 22 - [Net Rate Act 2] after a reset.)

Default:

0 = Autodetect

Values:

0 = Autodetect
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
5 = Disabled

Type:

Read/Write

Reset Required:

Yes

Parameter

No.

Name and Description

Details

255 . 255 . 255 . 255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

255 . 255 . 255 . 255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]