Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

33

Configuring the Option Module

Chapter 3

1.

Depending on the type of server (BOOTP or DHCP) being used, set
Device Parameter 05 - [Net Addr Sel] to either “2” (BOOTP) or “3”
(DHCP) respectively.

2.

Note the option module’s hardware Ethernet Address (MAC), which will
be used in step 7.

There are two ways to do this:

Locate the option module’s hardware Ethernet Address (MAC) on the
module’s product data nameplate label (

Figure 8

) located on the

backside of the circuit board.

Figure 8 - Option Module Hardware Address Label Location

Use the HIM to scroll to the drive Port in which the option module is
installed and access the option module’s DIAGNOSTIC folder screen.
Then scroll to Diagnostic Items 49…54 (HW Addr 1…6) to view the
option module’s hardware Ethernet Address (MAC).

3.

On a computer connected to the EtherNet/IP network, start the
BOOTP/DHCP software.

Value

Setting

1

Parameters

2

BOOTP

3

DHCP (default)

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Edit Net Addr Sel

DHCP

3

1 << 3

Ethernet Address (MAC)
label location

Backside of
circuit board