Resetting the option module – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 49

Advertising
background image

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

49

Configuring the Option Module

Chapter 3

Resetting the Option Module

Changes to switch and jumper settings and some option module parameters
require you to reset the option module before the new settings take effect. You
can reset the option module by power cycling the drive or by using

Device

Parameter 25 - [Reset Module]

.

Set

Device Parameter 25 - [Reset Module] to “1” (Reset Module).

When you enter “1” (Reset Module), the option module will be immediately
reset. An alternate method to reset the module is by power cycling the drive.
When you enter “2” (Set Defaults), the option module will set ALL of its

Device

and

Host parameters to their factory default values. (This is the same as pressing

the ALL

soft key when using the MEMORY folder method described in

Restoring Option Module Parameters to Factory Defaults on page 50

.) After

performing a Set Defaults, you must enter “1” (Reset Module) or power cycle the
drive so that the new values take effect. Thereafter, this parameter will be restored
to a value of “0” (Ready).

ATTENTION: Risk of injury or equipment damage exists. If the option module is
transmitting control I/O to the drive, the drive may fault when you reset the
option module. Determine how your drive will respond before resetting the
option module.

IMPORTANT

When operating the option module in Tap mode, Host parameters are NOT
supported, so only Device parameters are reset to their factory default values.

IMPORTANT

When performing a Set Defaults, the drive may detect a conflict and then not
allow this function to occur. If this happens, first resolve the conflict and then
repeat a Set Defaults action. Common reasons for a conflict include the drive
running or a controller in Run mode.

TIP

If your application allows, you can also reset the option module by cycling
power to the drive (resetting the drive) or by using the HIM’s Reset Device
function located in the drive’s DIAGNOSTIC folder.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Edit Reset Module

Ready

0

0 << 2