Chapter 4

Configuring the I/O

1.

Open the drive General tab dialog box.

2.

Click Change to open the Module Definition dialog box.

3.

Select the appropriate Electronic Keying for your application.

There are three Electronic Keying choices available in the Module
Definition dialog box in the Drive AOP, but only two are recommended
with ADC.

Electronic Keying
Selection

Recommendation

Exact Match

This selection should only be used if:

Your system design specification requires that a replacement drive/peripheral be

identical—down to the Minor revision of firmware (x.xxx).

You will be implementing Firmware Supervisor upgrade support in addition to

ADC. ControlFLASH firmware kits for the revision of firmware used for each drive/
peripheral must be installed on the computer running RSLogix 5000 software.
Upgrade files can be downloaded from:

http://www.ab.com/support/abdrives/webupdate