Viewing option module diagnostic items, Diagnostic items for adapter mode operation – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 118

Advertising
background image

118

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

Chapter 7

Troubleshooting

Viewing Option Module
Diagnostic Items

If you encounter unexpected communication problems, the option module’s
diagnostic items may help you or Rockwell Automation personnel troubleshoot
the problem. Option module diagnostic items can be viewed with the PowerFlex
20-HIM-A6 or 20-HIM-C6S HIM, DriveExplorer software, version 6.01 or
later, or DriveExecutive software, version 5.01 or later. For details on viewing
diagnostic items with the HIM, see the PowerFlex 20-HIM-A6/-C6S HIM
(Human Interface Module) User Manual, publication

20HIM-UM001

.

Diagnostic Items for Adapter Mode Operation

IMPORTANT

Some diagnostic items are not applicable when operating the option module
in Adapter mode while others are not applicable in Tap mode. Therefore, these
non-applicable diagnostic items are labeled “Reserved” in

Table 10

and

Table 11

.

Table 10 - Adapter Mode Diagnostic Items

No.

Name

Description

1

Common Logic Cmd

The present value of the Common Logic Command being transmitted to the drive by this option module.

2

Prod Logic Cmd

The present value of the Product Logic Command being transmitted to the drive by this option module.

3

Reference

The present value of the Reference being transmitted to the drive by this option module.

4

Common Logic Sts

The present value of the Common Logic Status being received from the drive by this option module.

5

Prod Logic Sts

The present value of the Product Logic Status being received from the drive by this option module.

6

Feedback

The present value of the Feedback being received from the drive by this option module.

7

Input Size

The size of the input image in bytes transferred from the network to the drive.

8

Output Size

The size of the output image in bytes transferred from the drive to the network.

9

DL Fr Net Avail

The number of Host DL From Net xx Datalinks currently available to the option module.

10

DL To Net Avail

The number of Host DL To Net xx Datalinks currently available to the option module

11

DL Fr Net 01 Val

The present value of respective Host DL From Net xx parameter being transmitted to the drive by this
option module. (If not using a Datalink, its respective value should be zero.)

12

DL Fr Net 02 Val

13

DL Fr Net 03 Val

14

DL Fr Net 04 Val

15

DL Fr Net 05 Val

16

DL Fr Net 06 Val

17

DL Fr Net 07 Val

18

DL Fr Net 08 Val

19

DL Fr Net 09 Val

20

DL Fr Net 10 Val

21

DL Fr Net 11 Val

22

DL Fr Net 12 Val

23

DL Fr Net 13 Val

24

DL Fr Net 14 Val

25

DL Fr Net 15 Val

26

DL Fr Net 16 Val