Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

47

Configuring the Option Module

Chapter 3

Changes to these parameters take effect immediately. A reset is not required.

If communication is disrupted and then is re-established, the drive will
automatically receive commands over the network again.

Setting the Fault Configuration Parameters

When setting

Host Parameter 33 - [Comm Flt Action], 34 - [Idle Flt Action],

35 - [Peer Flt Action]

or 36 - [Msg Flt Action] to “Send Flt Cfg,” the values in

the following parameters are sent to the drive after a communication fault, idle
fault, peer I/O fault, and/or explicit messaging for drive control fault occurs. You
must set these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not required.

Option Module Host Parameter

Description

Parameter 37 - [Flt Cfg Logic]

A 32-bit value sent to the drive for Logic Command.

Parameter 38 - [Flt Cfg Ref]

A 32-bit REAL (floating point) value sent to the drive for Reference.

Parameter 39 - [Flt Cfg DL 01]

through

Parameter 54 - [Flt Cfg DL 16]

A 32-bit integer value sent to the drive for a Datalink. If the destination of the
Datalink is a REAL (floating point) parameter, you must convert the desired
value to the binary representation of the REAL value. (An internet search of
“hex to float” provides a link to a tool to do this conversion.)