Link 2 status indicator—tap mode, Link 3 status indicator—tap mode – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 117

Advertising
background image

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

117

Troubleshooting

Chapter 7

LINK 2 Status Indicator—Tap Mode

This green/yellow bicolor LED indicates the status of the ENET2 network port
as shown in the table below.

LINK 3 Status Indicator—Tap Mode

This green/yellow LED indicates the status of the ENET3 (DEVICE) network
port as shown in the table below.

Status

Cause

Corrective Action

Off

The option module is not properly connected to the network.

Securely connect the option module to the network using an Ethernet cable.
Also, make sure the Ethernet cable is correctly connected to the Ethernet
connector.

Steady Green

ENET2 network port has a 100 Mbps network link, but no activity.

No action required.

Flashing Green

ENET2 network port has a 100 Mbps network link with activity.

No action required.

Steady Yellow

ENET2 network port has a 10 Mbps network link, but no activity.

No action required.

Flashing Yellow

ENET2 network port has a 10 Mbps network link with activity.

No action required.

Status

Cause

Corrective Action

Off

The option module is not properly connected to the network.

Securely connect the option module to the network using an Ethernet cable.
Also, make sure the Ethernet cable is correctly connected to the Ethernet
connector.

Steady Green

ENET3 network port has a 100 Mbps network link, but no activity.

No action required.

Flashing Green

ENET3 network port has a 100 Mbps network link with activity.

No action required.

Steady Yellow

ENET3 network port has a 10 Mbps network link, but no activity.

No action required.

Flashing Yellow

ENET3 network port has a 10 Mbps network link with activity.

No action required.

Advertising