Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 45

Advertising
background image

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

45

Configuring the Option Module

Chapter 3

7.

If a Logic Command is being sent, use

Device Parameter 30 - [Logic Src

Cfg]

to set the number of the Datalink that contains the Logic Command

within the range defined by

Device Parameter 28 - [DLs Fr Peer Cfg].

For example, if

Device Parameter 28 - [DLs Fr Peer Cfg] is set to receive

five Datalinks (Datalinks 12 through 16) and the first of those five
Datalinks (Datalink 12) contains the Logic Command, set

Device

Parameter 30 - [Logic Src Cfg]

to a value of “1.” Otherwise, set Parameter

30 to a value of “0.” For Logic Command bit definitions, see

Appendix D

or the drive documentation.

8.

If a Reference is being sent, use

Device Parameter 31 - [Ref Src Cfg] to set

the number of the Datalink that contains the Reference within the range
defined by

Device Parameter 28 - [DLs Fr Peer Cfg].

For example, if

Device Parameter 28 - [DLs Fr Peer Cfg] is set to receive

five Datalinks (Datalinks 12 through 16) and the second of those five
Datalinks (Datalink 13) contains the Reference, set

Device Parameter 31 -

[Ref Src Cfg]

to a value of “2.” Otherwise, set Parameter 31 to a value of

“0.”

9.

In each PowerFlex 750-Series slave drive, set drive parameter 308 -
[Direction Mode] to “0” (Unipolar) to be sure that it properly follows the
master drive’s speed reference and commanded direction.

10.

Reset the option module (see

Resetting the Option Module on page 49

) so

that changes to

Device Parameter 28 - [DLs Fr Peer Cfg] take effect.

11.

Set

Device Parameter 37 - [Fr Peer Enable] to a value of “2” (Custom).

Value

Setting

0

Off (Default)

1

Cmd/Ref

2

Custom

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Edit Fr Peer Enable

Off

0

0 << 2