22

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

Chapter 2

Installing the Option Module

The Node Address switch settings can be verified by viewing Diagnostic Item
number 73 (

page 120

or

page 122

) with a PowerFlex 20-HIM-A6 or 20-HIM-

C6S HIM, DriveExplorer software, or DriveExecutive software. Also, you can
use

Device Parameter 06 - [Net Addr Src], a read-only parameter, to verify the

selected setting for

Device Parameter 05 - [Net Addr Sel].

Connecting the Option
Module to the Drive

The option module is connected to the drive differently depending on the mode
in which the option module is operated.

When Operating in Adapter Mode

Install the option module in the PowerFlex 750-Series drive control pod in Port
4, 5 or 6. For more installation details, see the Network Communication Option
Card Installation Instructions, publication

750COM-IN002

, provided with the

option module.

When Operating in Tap Mode (only with PowerFlex 755 drives)

Install the option module in the PowerFlex 755 drive control pod in only Port 4
or 5. (When operating in Tap mode, drive Port 6 cannot be used.) For more
installation details, see the Network Communication Option Card Installation
Instructions, publication

750COM-IN002

, provided with the option module.

888

Resets the option module network node address to factory defaults. Thereafter, the drive must be
powered down, the Node Address switches must be set to a correct value (001…254), and then the
drive must be powered up again to accept the new address.

Any other
setting

Disables the Node Address switches, and requires using Device Parameter 05 - [Net Addr Sel] to
select the source for the option module’s network node address:
1 = Parameters of the option module
2 = BOOTP server
3 = DHCP server (default)

Settings

Description

IMPORTANT

Remove power from the drive before installing the option module in the drive
control pod.

IMPORTANT

After inserting the option module into drive Port 4, 5 or 6, make sure to tighten
the module screws to the pod mounting bracket to properly ground the
module to the drive. Torque both screws to 0.45…0.67 N•m (4.0…6.0 lb•in).

IMPORTANT

After inserting the option module into PowerFlex 755 drive Port 4 or 5 only,
make sure to tighten the module screws to the control pod bracket to properly
ground the module to the drive. Torque both screws to 0.45…0.67 N•m
(4.0…6.0 lb•in).