Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

Chapter 3

Configuring the Option Module

Restoring Option Module
Parameters to Factory
Defaults

As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using

Device Parameter 25 -

[Reset Module]

described in

Resetting the Option Module on page 49

. The

MEMORY folder method provides two ways to restore the option module
Device and Host parameters:

ALL—restores ALL option module

Device and Host parameters to their

factory default values.

MOST—restores MOST option module

Device and Host parameters—

except the following which are used for network setup:

Device Parameter 05 - [Net Addr Sel]

Device Parameters 07 through 10 - [IP Addr Cfg 1-4]

Device Parameters 11 through 14 - [Subnet Cfg 1-4]

Device Parameters 15 through 18 - [Gateway Cfg 1-4]

Device Parameter 19 - [Net Rate Cfg 1]

Device Parameter 21 - [Net Rate Cfg 2]

Device Parameter 23 - [Net Rate Cfg 3] (Tap mode only)

Follow these steps to restore option module

Device and Host parameters to their

factory default values.

1.

Access the Status screen, which is displayed on HIM powerup.

2.

Use the

or

key to scroll to the Port in which the option

module is installed.

3.

Press the

key to display its last-viewed folder.

4.

Use the

or

key to scroll to the MEMORY folder.

5.

Use the

or

key to select Set Defaults.

6.

Press the

(Enter) key to display the Set Defaults pop-up box.

7.

Press the

(Enter) key again to display the warning pop-up box to

reset

Device and Host parameters to their factory default values.

8.

Press the MOST

soft key to restore MOST Device and Host parameters to

factory defaults or press the ALL

soft key to restore ALL parameters. Or

IMPORTANT

When operating the option module in Tap mode, Host parameters are NOT
supported, so only Device parameters are reset to their factory default values.

00

Stopped

0.00 Hz

AUTO

Host Drive

240V

4.2A

Rev 3.002 Ser. A

ESC

REF

TEXT

F

PAR#