Chapter 3

Configuring the Option Module

Setting Web Page Access

By using a web browser to access the IP address set for the option module, you
can view the option module web pages for information about the module, the
drive and other DPI devices connected to the drive, such as HIMs or converters.

By default, the option module web pages are disabled. To enable the option
module web pages, set

Device Parameter 26 - [Web Enable] to “1” (Enabled).

For more details on the option module web pages, see

Chapter 8

, Viewing

Option Module Web Pages.

In Adapter mode, the option module can be configured to automatically send e-
mail messages to desired addresses when selected drive faults occur and/or are
cleared, and/or when the option module takes a communication or idle fault
action.

Bit 0 of

Device Parameter 27 - [Web Features] is used to protect the configured

settings for e-mail messaging. By default, settings are not protected and the user
can make changes. To protect the configured settings, set the value of E-mail Cfg
Bit 0 to “0” (Disabled). You can unprotect the configuration by changing Bit 0
back to “1” (Enabled). E-mail messaging will always remain active regardless of
whether or not its settings are protected—unless e-mail messaging was

never

configured. For more information about configuring option module e-mail
messaging or to stop e-mail messages, see

Adapter Mode Configure E-mail

Notification Web Page on page 130

.

Bit 0 is the right-most bit. In the example above, it equals “1” (Enabled).

Changes to this parameter take effect immediately. A reset is not required.

IMPORTANT

Depending on its selected operating mode (Adapter or Tap), the option module
provides a unique set of web pages with different information.

Value

Description

0

Disabled (Default)

1

Enabled

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Edit Web Enable

Disabled

0

0 << 1

Bit

Description

0

E-mail Cfg (Default = 1 = Enabled)

1…15

Not Used

ESC

ENTER

Stopped

0.00 Hz

AUTO

F

Edit Web Features

xxxx xxxx xxxx xxx1

E-mail Cfg