Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

123

Troubleshooting

Chapter 7

Table 12 - Option Module Events

Code

Event Text

Description

Option Module Events

1

No Event

Text displayed in an empty event queue entry.

2

Device Power Up

Power was applied to the option module.

3

Device Reset

The option module was reset.

4

EEPROM CRC Error

The EEPROM checksum/CRC is incorrect, which limits option module functionality. Default parameter values must be loaded to clear this condition.

5

App Updated

The option module application firmware was updated.

6

Boot Updated

The option module boot firmware was updated.

7

Watchdog Timeout

The software watchdog detected a failure and reset the option module.

DPI Events

8

DPI Bus Off

A bus-off condition was detected on DPI.

9

DPI Ping Timeout

A ping message was not received on DPI within the specified time.

10

DPI Port Invalid

The option module was not connected to a valid port on a DPI product.

11

DPI Port Changed

The DPI port changed after startup.

12

DPI Host Reset

The drive sent a reset event message.

13

DPI Baud 125kbps

The option module detected that the drive was communicating at 125 Kbps.

14

DPI Baud 500kbps

The option module detected that the drive was communicating at 500 Kbps.

15

DPI Host Invalid

The option module was connected to an incompatible product.

16

DPI Dup Port

Another peripheral with the same port number is already in use.

17

DPI Type 0 Logon

The option module has logged in for Type 0 control.

18

DPI Type 0 Time

The option module has not received a Type 0 status message within the specified time.

19

DPI DL Logon

The option module has logged into a Datalink.

20

DPI DL Error

The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.

21

DPI DL Time

The option module has not received a Datalink message within the specified time.

22

DPI Ctrl Disable

The option module has sent a “Soft Control Disable” command to the drive.

23

DPI Ctrl Enable

The option module has sent a “Soft Control Enable” command to the drive.

24

DPI Msg Timeout

A Client-Server message sent by the option module was not completed within 1 second.

25

DPI Manual Reset

The option module was reset by changing its Reset Module parameter.

SI Events

26

SI Online

The option module has logged into the Serial Interface Communication.

27

SI Logon Error

The option module failed to log into the Serial Interface.

28

SI Comm Fault

The Serial Interface Communication has faulted.

Network Events

29-30

Reserved

31

Net Dup Address

The option module uses the same address as another device on the network.

32

Net Comm Fault

The option module detected a communication fault on the network.

33

Net Sent Reset

The option module received a reset from the network.

34

Net IO Close

An I/O connection from the network to the option module was closed.

35

Net Idle Fault

The option module received “idle” packets from the network.

36

Net IO Open

An I/O connection from the network to the option module has been opened.