55
Configuring the I/O
Chapter 4
Figure 10 - Example ControlLogix Controller EtherNet/IP Device-level Ring Network
Adding the Bridge to the I/O Configuration
To establish communication between the controller and option module over the
network, you must first add the ControlLogix controller and its bridge to the
I/O configuration.
1.
Start RSLogix 5000 software.
2.
From the File menu, choose New to display the New Controller dialog
box.
a. Choose the appropriate choices for the fields in the dialog box to match
your application.
b. Click OK.
The RSLogix 5000 dialog box reappears with the treeview in the left
pane.
3.
In the treeview, right-click the I/O Configuration folder and choose New
Module.
IP Address 10.91.96.80
ControlLogix Controller with
1756-EN2TR Bridge
IP Address 10.91.96.101 (1st Drive)
PowerFlex 750-Series Drives
(each a with 20-750-ENETR Option Module)
Computer with
Ethernet Connection
1783-ETAP
1783-ETAP
To other
EtherNet/IP
networks