Instance attributes – Rockwell Automation 20-750-ENETR PowerFlexDual-Port EtherNet/IP Option Module User Manual

Page 174

Advertising
background image

174

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012

Appendix C

EtherNet/IP Objects (Adapter mode only)

Instance Attributes

Attribute ID

Access Rule Name

Data Type

Description

0

Get

Full/All Information

STRUCT of:

BOOL[32]
CONTAINER

(1)

CONTAINER
CONTAINER
CONTAINER
UINT
UINT
STRING[4]
UINT
UINT
UINT
INT
UDINT
STRING[16]

Descriptor (see

page 166

)

Value
Minimum value
Maximum value
Default value
Pad Word
Pad Word
Units (for example, Amps, Hz)
Multiplier

(2)

Divisor

(2)

Base

(2)

Offset

(2)

Link (source of the value) (0 = no link)
Diagnostic name text

1

Get/Set

Value

Various

Diagnostic item value

2

Get

International Diagnostic
Item Text

Struct of:

STRINGN
STRINGN

Diagnostic name text
Diagnostic units text

3

Get

International Full Read All

STRUCT of:

BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
UINT
UINT
UINT
UINT
UINT
INT
UDINT
BOOL[32]
STRINGN
STRINGN

Descriptor
Value
Minimum
Maximum
Default
Pad word
Pad word
Multiplier
Divisor
Base
Offset
Pad
Extended descriptor
Diagnostic name text
Diagnostic units text

(1) A CONTAINER is a 32-bit block of data that contains the data type used by a value. If signed, the value is sign extended. Padding is used in the

CONTAINER to be sure that it is always 32-bits.

(2) This value is used in the formulas used to convert the value between display units and internal units. See

Formulas for Converting on

page 168

.

Advertising