Log threshold configuration, Archive disk threshold configuration – Rockwell Automation 1756-HIST2G Historian ME 2.1  User Manual

Page 110

Advertising
background image

F

ACTORY

T

ALK

H

ISTORIAN

ME M

ODULE

U

SER

S

G

UIDE

100

Log Threshold Configuration

The Log Threshold Configuration section allows you to specify a warning level for

log files. The range is 95-99%, and the default is 95%.

When the log storage reaches its configured threshold, the FactoryTalk Historian ME

deletes older log files and logs a message in the System Log page:

<full path> has been removed because the /mnt/log partition is
full

.”

Archive Disk Threshold Configuration

The Archive Disk Threshold Configuration section allows you to specify a warning

level for archive disk usage. The range is 95-99%, and the default is 95%.

When the archive disk reaches its configured threshold, FactoryTalk Historian ME

stops Data Collection and logs a message in the System Log page:

“Stopping Data Collection because one or more partitions is full.”

It also deletes pimesslogfile located under /mnt/appdata/dat and logs a message in the

System Log page:

<full path> has been removed because the /mnt/appdata partition is
full.

Stopping Data Collection allows the module to process events from transient event

files to archive storage and make more storage space available.