The Exception Minimum (ExcMin) attribute is a deadband after the previous value.

This is used to suppress noise. It is specified in seconds. A new data value that is

received before the end of the ExcMin interval will be discarded.

E

XCEPTION

M

AXIMUM

The Exception Maximum (ExcMax) attribute puts a limit on the length of time that

values can be discarded due to exception testing. For example, it is possible for the

incoming data to be a single value for many days. If ExcMax is set to 28800 seconds

(8 hours) then a value will not be discarded due to exception if the previous event

timestamp was more than 28800 seconds before that. Note that the Data Collection

service does not manufacture data. If there are no incoming values within 28800

seconds, then nothing will be passed to the FactoryTalk Historian ME server.

Compression Filtering

The Snapshot subsystem uses compression filtering to determine which events it

should pass to the archive for storage. The point of compression filtering is to store

just enough data to accurately reproduce the original signal.
For example, in the following illustration, all the events fall on the same straight line.

In a simple case like this, you do not actually need to store all the points on the line. If

you store just two points, you can exactly recreate the point value for any other time.

This line can be reconstructed from any two of these events, so the most efficient

storage would be to store only the first and last events (A and B) rather than storing

all the events. Furthermore, no accuracy is sacrificed. If a user wants to retrieve the

value at any point along the line, it can be interpolated from the values that have been

stored.

TIME

ENG Units