Managing points, Using the add points wizard, 5 • managing points – Rockwell Automation 1756-HIST2G Historian ME 2.1  User Manual

Page 75

Advertising
background image

65

5

Managing Points

This chapter contains the following sections:

“Using the Add Points Wizard”

“Using the Tag Browser to Create Points”

“Manually Creating and Editing Points”

“Defining Point Attributes”

“Configuring Scan Types”

“Configuring Trigger Input and Output Points”

“Working with Scan Classes”

Using the Add Points Wizard

To start the wizard, click Manage Points in the top navigation bar, then click the Add
Points Wizard

in the left navigation bar. The Add Points Wizard guides you through

the process of discovering and collecting tags in controllers, creating points, and then

storing the data from the controller in the FactoryTalk Historian ME. You can create
a maximum of 2500 data points per FactoryTalk Historian ME.

Do not use the web interface or the FactoryTalk Historian SE System Management Tools
(SMT) Tag Configurator to change the configuration or points when the module is
collecting data or data interruption may result.

Never delete the FTMEScanRateDefinition tag or other system-generated tags with
names such as “bae9cf24-c8b3-46c0-ad5d-a64df2174ed9” and values such as “No Data”.
The FTMEScanRateDefinition tag is a system-generated tag that contains scan class
definitions. If it is deleted all scan class definitions will be removed. Deleting other system-
generated tags will cause the System Log to overflow with error messages.

Every time point configuration(s) are changed you should expect data interruption.

Advertising
This manual is related to the following products: