Data Transfer Sample Scenario

The FactoryTalk Historian ME 1G and 2G modules use a CompactFlash memory

card to store logged data. Once the module archive becomes full of logged data, it

automatically begins overwriting the oldest data. To preserve data collected by the

module for long-term storage, you can transfer it to the FactoryTalk Historian SE

server.
This section provides a sample scenario for transferring the data logged in the

FactoryTalk Historian ME module to the FactoryTalk Historian SE server. It includes

the following sections:

“Configuring Data Transfer Settings”

“Initiating Data Transfer”

“Using FactoryTalk Historian DataLink”

Configuring Data Transfer Settings

For the FactoryTalk Historian SE server to receive data from a FactoryTalk Historian

ME module, you must ensure that:

Necessary licenses are installed and assigned on the FactoryTalk Historian SE

server.

Network connections and associated security configurations are set up and

functioning properly between the FactoryTalk Historian ME and the FactoryTalk

Historian SE.

Trust connections between the FactoryTalk Historian ME module and the

FactoryTalk Historian SE server are configured for data transfer and webs
(application).

Sufficient disk space is available on the FactoryTalk Historian SE server.

Start time of the archives on the FactoryTalk Historian SE server must be earlier

than that of the data to be transferred.

See “Managing Security Trusts” for more details on trusts.