Managing Time

To manage time in the FactoryTalk Historian ME, click Advanced in the main

navigation bar, and then click Time Management in the left navigation bar. The

Modules’s Current Time field displays the FactoryTalk Historian ME’s current time.

Precise timing is critical for most module services including Data Collection, Data

Transfer, and Data Storage because all events are time-stamped and the order of these

events is important. To provide accurate time for these services, you can configure

the module to synchronize time with a variety of time sources.
At boot time, the module will read and automatically synchronize its real-time clock

with these external time sources. After successfully synchronizing with a time source

at boot time, the module will achieve runtime time precision by periodically
resynchronizing with the time source.

When changing the module time, do not change the module time to a time earlier than
the current module time if Data Collection has already been started.