FactoryTalk Historian ME ProcessBook trend with a vertical scale of database.

This attribute is not used for non-numeric points.

Step

Defines how numeric archived values are interpolated. The Step flag affects only

numeric points. The default behavior, OFF (0), treats archived values as a

continuous signal. Adjacent archived values are linearly interpolated. For

example, at 12:00:00, the value 101.0 is archived and at 12:01:00, the value 102.0

is archived. A request for the archive value at 12:00:30 would return 101.5.
Step ON (1) treats the archived values discretely. Adjacent archived values are not

interpolated; an archived value is assumed constant until the next archived value.

For example:

- At 12:00:00, the value 101.0 is archived.
- At 12:01:00, the value 102.0 is archived.

A request for the value at 12:00:30 would return 101.0.
In general, data coming from continuous signals should be archived in points with

the step flag OFF. Examples might include signals from thermocouples, flow

meters, etc. Data coming from discrete measurements should be archived in

points with the step flag ON. Examples are sampled laboratory data, batch charge

weight. In addition, the step flag affects the compression calculation. When it is

ON (1), a linear change of value greater than or equal to CompDev attribute

passes compression. This is essentially the same as the exception reporting. When

the step flag is OFF, the complete swinging door algorithm is applied.

Shutdown

Specifies whether the FactoryTalk Historian ME will automatically add a

shutdown event with the time stamp of the FactoryTalk Historian ME server

shutdown. In some cases, it is useful to record to

FactoryTalk

Historian ME points

when the archive was shut down to indicate a gap in the Data Collection.
Set Shutdown to ON (1) to record shutdown events for this data point (tag). The

default is ON.

Compressing

The FactoryTalk Historian ME uses compression specifications to filter the data

passed from the Snapshot subsystem to the Archive subsystem. The Snapshot

subsystem stores the most recent value for each data point. This most recent value

is called the Snapshot for that point. The Snapshot subsystem uses compression