Data Transfer Issues

This section contains information that may help you troubleshoot FactoryTalk
Historian ME Data Transfer.

For any issue, follow the guidelines provided in the “General Guidelines” section
of this appendix.

Data Transfer

Symptom

Solution

The System Status

section on the Home

page shows that Data

Transfer is in

“Stopped” mode:

Go to the Advanced tab to view the System Log page. Check

the log for messages about the issue and export log data.

Go to the Configure Historian tab. On the Data Transfer

page, click [Start] to restart Data Transfer.

If Data Transfer does not start:

Ensure that the FactoryTalk Historian SE host name or

IP address is correct.

Ensure that all security settings, including trust connec-

tions (if required), have been properly configured.

Click [Test Connection] to ensure a connection to the

FactoryTalk Historian SE can be established.

The System Status

section on the Home

page shows that Data

Transfer is in “Error”

mode:

Go to the Advanced tab to view the System Log page.

Check the log for messages about the issue and export log

data.

Check the module STS LED light. Flashing red indicates

that Data Transfer is inactive (and Data Collection is

active.)

Go to the Web Diagnostics Firmware tab, and check the
Data Transfer

page. Process information can confirm

whether or not Data Transfer is in a undesirable state.

N/A indicates an error state.

Download log files that will assist in troubleshooting as

described in “General Guidelines”.

Reboot the module.

Contact Technical Support if the issues persists.