The System Status
section on the Home
page shows that Data
Collection is in
“Error” mode:
Check the module STS LED light. Solid red indicates that
Data Collection is inactive.
Go to the Advanced tab to view the System Log page.
Check the log for messages about the issue and export log
data.
Go to the Web Diagnostics Firmware tab, and check the
Data Collection
page. Process information can confirm
whether or not Data Collection is in a undesirable state.
N/A indicates an error state.
Download additional information that will assist in trouble-
shooting as described in “General Guidelines”.
Reboot the module.
Contact Technical Support if the issues persists.
Data Collection
Symptom
Solution