Rockwell Automation 1756-HIST2G Historian ME 2.1  User Manual

Page 99

Advertising
background image

5 • M

ANAGING

P

OINTS

89

Allows a space, comma, or semicolon to separate trigger definitions.

I

NSTRUMENT

T

AG

The Instrument Tag field is used for the full path to the controller. If a source tag

receives events from a controller, the tag in this field will read (or write back) events

from the controller. The tag name syntax is:

<controller_name>.<tag_name>

S

OURCE

T

AG

The Source Tag field is used to designate a trigger tag. Enter a trigger tag name for

the triggered Trigger Input or Output point.

Keyword

Trigger

Condition

Description

Example

TRIG

The condition is always Any.

EVENT

Any

EVENT

Nonzero

Trigger on any non-zero

value.

An event is triggered on a

value change from “Pt

Created” to 1 but it is not

triggered on a value

change from 1 to “bad

Input”.

EVENT

Anychange

Trigger on any change as

long as the value of the

current event is different

from the value of the

previous event.

An event will be triggered

on a value change from 0

to “bad Input” or from

“bad Input” to 0.

EVENT

Increment

Trigger on any increase in

value.

An event will be triggered

on a value change from 0

to 1.

EVENT

Decrement

Trigger on any decrease in

value.

An event will be triggered

on a value change from 1 to

0.

Advertising