G • T

ROUBLESHOOTING

285

If Data Collection is

running on one or

more modules and

these modules are

transferring data to a

FactoryTalk Historian

SE, the FactoryTalk

Historian SE will

experience a large load

and overflow events if

Data Transfer is

stopped for some time

and then restarted:

To minimize the load and number of overflow events on the

FactoryTalk Historian SE, go to the Configure Historian tab.

On the Data Transfer page, reduce the Maximum Events per

Transfer value. This parameter controls the number of events

transferred.

If Data Transfer and

Data Collection are

running on one or

more modules, and

Data Transfer is

stopped and then

started on one module

after some time has

passed, the module

may experience data

interruption:

Restarting Data Transfer on the module may cause data

interruption because old timestamps cannot be written to

the current archive.

After it is restarted, ensure that Data Transfer remains run-

ning so that transferred events eventually match the archive

event timestamps.

Data Transfer

Symptom

Solution