In the sample scenario described in this chapter, a 2500 tag license has been assigned

against the FTMS point source in the FactoryTalk Administration Console for the

FactoryTalk Historian SE server.
1. Log into the in FactoryTalk Historian ME web interface as a FactoryTalk Security

user with Administrator privileges.

2. Click Configure Historian, and then click Data Transfer in the left navigation

bar of the web interface.

3. Enter the host name or IP address of the FactoryTalk Historian SE server in the

Host Server field. Rockwell suggests you use the host name.

4. Click [Test Connection].
5. Click [Save].

Values appear in the following fields:

FTHSE Licensed Points - the maximum number of points that have been

assigned within that FactoryTalk Historian SE server for FactoryTalk

Historian ME points. The values displayed here are read from the FactoryTalk

Historian SE server.

“FTMS” Points Available - the number of remaining licensed points that can

still be configured for Data Transfer. FTMS means FactoryTalk Historian
M

E-to-FactoryTalk Historian SE.

For example, when a 2500 tag license has been assigned in the FactoryTalk

Historian SE server and 1001 points are used against that license, 1499 points

remain to be configured for transfer. These 1499 points are available FTMS

points.

6. Make sure Auto Transfer is enabled. This feature is enabled by default.

Auto Transfer allows any point configured for Data Collection to be transferred

automatically to the FactoryTalk Historian SE server.