The Output point is associated with the trigger point by setting the Source Tag

attribute of the Output point equal to the tag name of the trigger point. An output

is triggered when a new value is sent to the snapshot of the trigger point. The new

value does not need to be different than the previous value that was sent to the

snapshot to trigger an output, but the timestamp of the new value needs to be

more recent than the previous value.

By writing a new value to the snapshot of the output point itself. The new value

need not be different from the previous value to trigger an output, but the

timestamp of the new value must be more recent than the previous value.

Point Attributes

The Point Property page contains three fields that are used for Trigger Input and

Output points:

Extended Description

Instrument Tag

Source Tag

Note that:

The Scan Rate is not applicable to the Trigger Input tag.

The Scan On drop-down menu must be set to On.

The trigger tag name must be in single quotes.

E

XTENDED

D

ESCRIPTION

: T

RIGGER

C

ONDITIONS

The Extended Description field on the Point Property page is used for the trigger

condition and the keywords that indicate trigger condition: TRIG or EVENT. Ensure

that the words TRIG and EVENT are uppercase. Condition names are case-

insensitive.
The TRIG keyword:

Does not require any condition.

Has a default condition of Any.

Treats conditions other than Any as Any.

The EVENT keyword:

Requires a trigger condition for it to function properly.