If you can access the

FactoryTalk Historian

ME web client but cannot

log in:

First check that you are using the correct security

mode. By default, FactoryTalk Historian ME web

client uses Native security, with the administrative

user name piadmin.

If the module has been configured with FactoryTalk

Security (FTSecurity), you must ensure that the user

has been configured in FTSecurity. To find the cur-

rent security mode, go to the Web Diagnostics,
Firmware

Overview. Check the Security Mode sec-

tion for the configured security information.

Go to the FactoryTalk Historian ME Module Prop-

erties page in AOP. In the Configuration tab, click

[Reset Security].

If the administrator

forgets the login name

and/or password:

Reset security to factory settings.

Click Advanced

in the top navigation bar, and then click Restore
Defaults

. In the Security Reset section, press

[Security Reset].

or

Go to the FactoryTalk Historian ME Module Prop-

erties page in AOP. In the Configuration tab, click

[Reset Security].

If you using the host

name as a URL and

cannot access the web

client:

Try to navigate to the page using the IP address of

the module. If this works, then be sure that the host

name you typed in is not misspelled.

Check that the DNS server is running.

If the web home page is

slow to respond:

If you have downloaded a large .ACD file to the

controller at bootup time and tried to add more than

2500 points, you may need to wait for the module to

respond. If it does not respond after several minutes,

reboot the module.

Keep in mind that the module requires some initial-

ization time to respond to the controller.

Web Client Symptom

Solution