number of FactoryTalk Historian ME points that can be transferred to the

FactoryTalk Historian SE.

"FTMS" Points Available - the total number of points assigned by the license

minus the number of points that are already being transferred to the FactoryTalk

Historian SE server.

Setting Data Transfer Parameters

The Data Transfer service status is either started or stopped. Click the appropriate

button to either start or stop Data Transfer.

Maximum Events per Transfer

To configure FactoryTalk Historian ME for Data Transfer, enter the Maximum

Events Per Transfer for the maximum number of events that can be transferred to

FactoryTalk Historian SE per transfer session. The range is 5,000 to 150,000. The

default setting is 50,000.
If you change the Maximum Events Per Transfer value, you need to stop and restart

Data Transfer after you click [Save] for the change to take effect.
Status displays the current Data Transfer status (Running or Stopped). If necessary,

click [Start] or [Stopped] to start or stop Data Transfer.

Enable Auto Transfer

Clicking the Enable Auto Transfer checkbox provides immediate Data Transfer.

Clicking [Save] is not required. However, if you attempt to transfer points and the

FactoryTalk Historian SE is not licensed to receive the points, a message will be sent

to the system log:

“The new points number is greater than what is allowed by the
SE license. Please change to NonAutoTransfer mode.”

The configuration then switches to non-auto transfer mode, and you must manually

transfer points by selecting them one-by-one.