Time Management Issues

This section contains information that may help you troubleshoot FactoryTalk
Historian ME time management.

For any issue, follow the guidelines provided in the “General Guidelines” section
of this appendix.

Time Management

Symptom

Solution

You have forgotten the

module’s time

synchronization

source:

Go to Web Diagnostics, Hardware tab, Time Management

page. The time source is listed in the Time Source section.

The module is

synchronized to a

controller time source

and the controller time

is moving back,

causing the module

time to move back:

Correct the controller time. Download archives to save the

archive data with future timestamps.

Click [Repair Archive] that initially displays when the

module is rebooted. ([Repair Archive] indicates that your

system is in safe mode.) Do not delete the archive files.

The module is

synchronized to an

NTP time source, and

the module time is not

correct.

Check that the NTP server is running properly.

If the NTP server is running properly, check the NTP log;

this indicates if the NTP time was successfully synchro-

nized during initial configuration or not. If it was, then it

must be resynchronized. Navigate to the Advanced tab,
Time Management

screen. Select the NTP Server radio

button, re-enter the NTP server address, and click [Save].

This will reboot the module and may take several minutes

to complete. If the module was never successfully syn-

chronized, then you must do so now. Refer to “Managing

Time” for more information.

The module is

synchronized to a

Historian SE server

and the module time is

incorrect:

Verify that the FactoryTalk Historian SE is configured as an

NTP server. For more information, refer to “Managing

Time”.