Archive usage threshold configuration, Exception filtering – Rockwell Automation 1756-HIST2G Historian ME 2.1  User Manual

Page 111

Advertising
background image

6 • C

OLLECTING

D

ATA

101

Archive Usage Threshold Configuration

The Archive Usage Threshold Configuration section allows you to specify the

warning and critical levels for Data Storage.

Warning - a capacity percentage between 25 and 100 at which FactoryTalk

Historian ME will issue a warning. The default is 50%.

Critical - a capacity percentage between 25 and 100 at which FactoryTalk

Historian ME will issue a critical message. The default is 75%.
You can set FactoryTalk Historian ME to stop Data Collection when it reaches

this point. If you do not want Data Collection to stop, then you risk data

interruption when all archive files have been filled and the Data Collection
service begins overwriting the oldest data.

Exception Filtering

The purpose of Exception Filtering is for the Data Collection service to only collect

data you are interested in, rather than taxing the system by collecting a lot of data that

is not meaningful.
Exception filtering uses a deadband algorithm to determine whether to collect data

and store it in the FactoryTalk Historian ME archive. For each point, you can set

exception reporting specifications that create the deadband. The Data Collection

service throws out values that fall inside the deadband and does not pass it to the

archive.

You risk data interruption by checking the Stop Data Collection check box. Checking
this box automatically stops Data Collection if the critical capacity percentage is
reached.