To calculate the total events per second, tags divided by the scan rate have to be

summed up per scan class for the module:

For example, if the Data Collection configuration is based on two scan classes, one

with 200 tags at a 250ms scan rate and one with 600 tags at a 2s scan rate, the total

events per second is 1100.

200/250ms + 600/2sec <-> 200/.25sec + 600/2sec <-> 800 + 300 events/sec = 1100 events/sec

Time Synchronization

This section lists considerations related to time synchronization.

For information about how configure the FactoryTalk Historian SE as an NTP

time server, refer to Microsoft’s knowledgebase article “How to Configure an

Authoritative Time Server in Windows” at http://support.microsoft.com/kb/

816042/en-us
A sample public NTP server is located here: 0.north-america.pool.ntp.org.

Backup and Recovery

Module configuration data can be backed up to a compressed file.

Only the last version of the backup configuration is stored.

Do not edit the backup and recover XML files.

System Connectivity

This section lists considerations related to system connectivity.

The maximum number of modules per chassis is 2.

Number of controllers that can transfer data to one module is 4.